MT02648 Door/Window Contact

This describes the Z-Wave device MT02648, manufactured by Devolo with the thing type UID of devolo_mt02648_00_000.

Door/Window Contact

Channels

The following table summarises the channels available for the MT02648 Door/Window Contact.

Channel Channel Id Channel Type UID Category Item Type
Door / Window Status sensor_door sensor_door Door Contact
Sensor (temperature) sensor_temperature sensor_temperature Temperature Number
Sensor (luminance) sensor_luminance sensor_luminance Temperature Number
Alarm alarm_general alarm_general Door Switch
  battery-level system.battery-level    

Sensor (temperature)

Scale

Select the scale for temperature readings

Property Value      
Configuration ID config_scale      
Data Type TEXT   Default Value 0
Options Celsius (0)      
  Fahrenheit (1)      

Device Configuration

The following table provides a summary of the configuration parameters available in the MT02648 Door/Window Contact. Detailed information on each parameter can be found below.

Parameter Description
2: Basic Set Level Setting the BASIC command value to turn on the light.
3: PIR Sensitivity PIR sensitivity settings.
4: Light Threshold Setting the illumination threshold to turn on the light
5: Operation Mode Parameter to set the Operation Mode
6: Multi-Sensor Function Switch Parameter to set the sensor functions
7: Customer Function Parameter to set the Customer Function
8: PIR Re-Detect Interval Time Parameter to set the PIR Re-Detect Interval Time
9: Turn Off Light Time Parameter to set the Turn Off Light Time
10: Auto Report Battery Time Parameter to set the Auto Report Battery Time
11: Auto Report Door/Window State Time The interval time for auto reporting the door/window state
12: Auto Report Illumination Time The Interval time for auto reporting the illumination state
13: Auto Report Temperature Time The interval time for auto reporting the temperature state
20: Auto Report Tick Interval The interval time for each auto report tick
21: Temperature Differential Report The temperature differential to report
22: Illumination Differential Report The illumination differential to report
1: Reports  
2: Light Control  

2: Basic Set Level

Setting the BASIC command value to turn on the light.

Overview

The 0xFF(-1) means turn on the light. For dimmer equipment 1 to 100 means the light strength. 0 means turn off the light.

Property Value
Configuration ID config_2_1
Data Type INTEGER
Range -1 to 100
Default Value -1

3: PIR Sensitivity

PIR sensitivity settings.

Overview

0 means disable the PIR motion. 1 means the lowest sensitivity, 99 means the highest sensitivity. High sensitivity means can detected long distance, but if there is more noise signal in the environment, it will re-trigger too frequency. 

Property Value      
Configuration ID config_3_1      
Data Type INTEGER   Default Value 70
Options Disable PIR (0)      

4: Light Threshold

Setting the illumination threshold to turn on the light

Overview

When the event triggered and the environment illumination lower then the threshold, the device will turn on the light. 0 means turn off illumination detected function. And never turn on the light. 1 means darkest. 99 means brightest.100 means turn off illumination detected function. And always turn on the light.

Notice: In none test mode, only the value in 1 to 99 will enable the illumination detected function and update the illumination value. 

Property Value      
Configuration ID config_4_1      
Data Type INTEGER   Default Value 100
Options Disable (Light OFF) (0)      
  Disable (Light ON) (100)      

5: Operation Mode

Parameter to set the Operation Mode

Overview

Bit0: Reserve.

Bit1: 1 means enable test mode, 0 means disable normal mode. (Notice: This bit only effect by the DIP Switch setting to program mode.) 

Bit2: Disable the door/window function.

Bit3: Setting the temperature scale. 0: Fahrenheit, 1:Celsius

Bit4: Disable the illumination report after event triggered.

Bit5: Disable the temperature report after event triggered.

Bit6: Reserve.

Bit7: Disable the back key release into test mode.

Property Value      
Configuration ID config_5_1      
Data Type INTEGER      
Range 0 to 127   Default Value 0
Options Preset: Celsius and LED on = Bits: 00001010 = 10 (10)      

6: Multi-Sensor Function Switch

Parameter to set the sensor functions

Overview

Bit0: Disable magnetic integrate illumination.

Bit1: Disable PIR integrate Illumination.

Bit2: Disable magnetic integrate PIR (Default is Disable)

Bit3: When Bit2 is 0 (Enable), Are the device and the lighting in the same room? 0: In the same room(Default), 1: In the different room.

Notice: If this bit is 1, it is recommended also set the Bit1 to 1, cause the PIR triggered, doesn’t mean the people in that room.

Bit4: Disable delay 5 seconds to turn off the light, when door/window closed.

Bit5: Disable auto turn off the light, after door/window opened to turn on the light.

Notice: If bit2 is zero, this setting is useless. Notice: If the configuration No.9 is zero, this setting is useless.

Bit6: Reserve.

Bit7: Reserve.

Property Value
Configuration ID config_6_1
Data Type INTEGER
Range 0 to 127
Default Value 4

7: Customer Function

Parameter to set the Customer Function

Overview

Bit0: Reserve.

Bit1: Enable sending motion OFF report.

Note: Depends on the Bit4, 0: Report Notification CC, Type: 0x07, Event: 0xFE 1: Sensor Binary Report, Type: 0x0C, Value: 0x00

Bit2: Enable PIR super sensitivity mode.

Bit3: Enable don’t send out BASIC OFF after door closed.

Bit4: Notification Type, 0: Using Notification Report. 1: Using Sensor Binary Report.

Bit5: Disable Multi CC in auto report.

Bit6: Disable to report battery state when the device triggered.

Bit7: Reserve.

Property Value      
Configuration ID config_7_1      
Data Type INTEGER      
Range 0 to 127   Default Value 4
Options Preset: PIR Super Sensitivity and Binary Report = Bits: 00010100 = 20 (20)      

8: PIR Re-Detect Interval Time

Parameter to set the PIR Re-Detect Interval Time

Overview

In the normal mode, after the PIR motion detected, setting the re-detect time. 8 seconds per tick, default tick is 3 (24 seconds).

Setting the suitable value to prevent received the trigger signal too frequency. Also can save the battery energy.

Notice: If this value bigger than the configuration setting NO. 9. There is a period after the light turned off and the PIR not start detecting.

Property Value
Configuration ID config_8_1
Data Type INTEGER
Range 1 to 127
Default Value 3

9: Turn Off Light Time

Parameter to set the Turn Off Light Time

Overview

After turn on the lighting, setting the delay time to turn off the lighting when the PIR motion is not detected. 8 seconds per tick, default tick is 4 (32 seconds). 0 means never send turn off light command.

Property Value
Configuration ID config_9_1
Data Type INTEGER
Range 0 to 127
Default Value 4

10: Auto Report Battery Time

Parameter to set the Auto Report Battery Time

Overview

The interval time for auto report the battery level. 0 means turn off auto report battery. The default value is 12. The tick time can setting by the configuration No.20.

Property Value
Configuration ID config_10_1
Data Type INTEGER
Range 0 to 127
Default Value 12

11: Auto Report Door/Window State Time

The interval time for auto reporting the door/window state

Overview

The interval time for auto report the door/window state. 0 means turn off auto report door/window state. The default value is 12. The tick time can setting by the configuration No.20.

Property Value
Configuration ID config_11_1
Data Type INTEGER
Range 0 to 127
Default Value 12

12: Auto Report Illumination Time

The Interval time for auto reporting the illumination state

Overview

The interval time for auto report the illumination. 0 means turn off auto report illumination. The default value is 12. The tick time can setting by the configuration No.20.

Property Value
Configuration ID config_12_1
Data Type INTEGER
Range 1 to 127
Default Value 12

13: Auto Report Temperature Time

The interval time for auto reporting the temperature state

Overview

The interval time for auto report the temperature. 0 means turn off auto report temperature. The default value is 12. The tick time can setting by the configuration No.20.

Property Value
Configuration ID config_13_1
Data Type INTEGER
Range 1 to 127
Default Value 12

20: Auto Report Tick Interval

The interval time for each auto report tick

Overview

The interval time for auto report each tick. Setting this configuration will effect configuration No.10, No.11, No.12 and No.13. Caution: Setting to 0 means turn off all auto report function.

Property Value
Configuration ID config_20_1
Data Type INTEGER
Range 0 to 255
Default Value 30

21: Temperature Differential Report

The temperature differential to report

Overview

The temperature differential to report. 0 means turn off this function. The unit is Fahrenheit. Enable this function the device will detect every minutes. And when the temperature is over 140 degree Fahrenheit, it will continue report. Enable this functionality will cause some issue please see the detail in the “Temperature Report” section.

Property Value
Configuration ID config_21_1
Data Type INTEGER
Range 0 to 127
Default Value 1

22: Illumination Differential Report

The illumination differential to report

Overview

The illumination differential to report. 0 means turn off this function. The unit is percentage. Enable this function the device will detect every minutes. Enable this functionality will cause some issue please see the detail in the “Illumination Report” section.

Property Value
Configuration ID config_22_1
Data Type INTEGER
Range 0 to 99
Default Value 1

1: Reports

Property Value
Configuration ID group_1
Data Type TEXT
Range to

2: Light Control

Property Value
Configuration ID group_2
Data Type TEXT
Range to