MT2756 MT2756 Flood Sensor

This describes the Z-Wave device MT2756, manufactured by Devolo with the thing type UID of devolo_mt2756_00_000.

MT2756 Flood Sensor

Channels

The following table summarises the channels available for the MT2756 MT2756 Flood Sensor.

Channel Channel Id Channel Type UID Category Item Type
Binary Sensor sensor_binary sensor_binary Door Switch
Alarm (water) alarm_flood alarm_flood Door Switch
Alarm (burglar) alarm_burglar alarm_burglar Door Switch
  battery-level system.battery-level    

Device Configuration

The following table provides a summary of the configuration parameters available in the MT2756 MT2756 Flood Sensor. Detailed information on each parameter can be found below.

Parameter Description
1: Basic Set OFF Level Setting the BASIC command value
2: Basic Set ON Level Setting the BASIC command value
5: Disable the Flood function Operation mode
7: Customer Function Parameter to set the sensor functionsBit 0: ReserveBit 1: ReserveBit 2: ReserveBit 3: Disa…
10: Auto Report Battery Time The interval time for auto reporting the battery level
15: Auto Report Flood Time The interval time for auto report the flood state
20: Auto Report Tick Interval The interval time for auto reporting each tick.
1: Reports  
2: Light Control  

1: Basic Set OFF Level

Setting the BASIC command value

  • When the flood trigger off(0x00), send the BASIC CC to the group 2
Property Value
Configuration ID config_1_1
Data Type INTEGER
Range 0 to 255
Default Value 0

2: Basic Set ON Level

Setting the BASIC command value

  • When the flood trigger on(0xFF), send the BASIC CC to the group 2
Property Value
Configuration ID config_2_1
Data Type INTEGER
Range 0 to 255
Default Value 255

5: Disable the Flood function

Operation mode

  • 0: Flood function is enabled
  • 1: Flood function is disabled
Property Value      
Configuration ID config_5_1      
Data Type INTEGER   Default Value 0
Options Flood function is enabled (0)      
  Flood function is disabled (1)      

7: Customer Function

Parameter to set the sensor functionsBit 0: ReserveBit 1: ReserveBit 2: ReserveBit 3: Disable send out BASIC OFF after the flood event clearedBit 4: Notification Type. 0:Using Notification Report, 1:Using Sensor Binary ReportBit 5: Disable Multi CC in aut

Property Value
Configuration ID config_7_1
Data Type INTEGER
Range 0 to 255
Default Value 0

10: Auto Report Battery Time

The interval time for auto reporting the battery level

  • 0 = Turn off auto report battery.
  • 1-127 = Number of ticks. The default value is 12. The tick time can be set by configuration No. 20.
Property Value
Configuration ID config_10_1
Data Type INTEGER
Range 0 to 127
Default Value 12

15: Auto Report Flood Time

The interval time for auto report the flood state

  • 0 = Turn off auto report
  • 1-127 = Number of ticks. The default value is 12. The tick time can be set by configuration No. 20.
Property Value
Configuration ID config_15_1
Data Type INTEGER
Range 0 to 127
Default Value 12

20: Auto Report Tick Interval

The interval time for auto reporting each tick.

  • 0 = Turn off all auto report function.
  • 1-255 = Number of ticks. Setting this configuration will effect configuration Nr. 10 and No. 15.
Property Value
Configuration ID config_20_1
Data Type INTEGER
Range 0 to 255
Default Value 30

1: Reports

Property Value
Configuration ID group_1
Data Type TEXT
Range to

2: Light Control

Property Value
Configuration ID group_2
Data Type TEXT
Range to

Did you spot an error in the above definition or want to improve the content? You can edit the database here.