FGR222 Roller Shutter 2

This describes the Z-Wave device FGR222, manufactured by Fibargroup with the thing type UID of fibaro_fgr222_24_024.

Roller Shutter 2

Overview

The device allows for controlling motors of roller blinds, awnings, venetian blinds, gates and others, which are single phase AC powered.

Inclusion Information

Fibaro Roller Shutter may be included into the Z-Wave network via the B-button or a push button connected to the S1 terminal. In addition, the module may be included in auto inclusion mode, by simply connecting the power supply.

Automatic Z-Wave network inclusion:

  1. Make sure the power supply is disconnected and a Roller Shutter is located within a direct Z-Wave network’s main controller communication range.
  2. Set the main controller into the learn mode (see main controllers operating manual).
  3. Connect the power supply to include the Roller Shutter in auto inclusion mode. 4) Fibaro Roller Shutter will be automatically detected and included into the Z-Wave network.

To disable the auto inclusion mode, press the B-button briefly, after connecting the module to the power supply.

Manual Z-Wave network inclusion: 

  1. Connect the power supply.
  2. Set the main controller into the learn mode (see main controllers operating manual).
  3. Triple click the B-button or a push button connected to the S1 terminal.
  4. Fibaro Roller Shutter will be detected and included into the Z-Wave network.

Exclusion Information

  1. Make sure the module is connected to the power supply.
  2. Set the main controller into the learn mode (see main controllers operating manual).
  3. Triple click the B-button or a push button connected to the S1 terminal.

Wakeup Information

device has mains power, doesn’t sleep.

Channels

The following table summarises the channels available for the FGR222 Roller Shutter 2.

Channel Channel Id Channel Type UID Category Item Type
Switch switch_binary switch_binary Switch Switch
Blinds Control blinds_control blinds_control Blinds Rollershutter
Scene Number scene_number scene_number   Number
Sensor (power) sensor_power sensor_power Energy Number
Electric meter (watts) meter_watts meter_watts Energy Number
Electric meter (kWh) meter_kwh meter_kwh Energy Number

Blinds Control

Invert control

Invert the blinds control

Property Value      
Configuration ID config_invert_control      
Data Type BOOLEAN   Default Value false
Options Yes (true)      
  No (false)      

Invert percentage value

Invert the blinds percentage value

Property Value      
Configuration ID config_invert_percent      
Data Type BOOLEAN   Default Value false
Options Yes (true)      
  No (false)      

Step duration

Sets the dim rate speed
Values from 1 to 127 are defined in seconds, while values from 128 to 254 are defined in minutes.

Property Value      
Configuration ID config_duration      
Data Type INTEGER      
Range 1 to 254   Default Value 255
Options Device Default (255)      
  Change Instantly (0)      

Device Configuration

The following table provides a summary of the configuration parameters available in the FGR222 Roller Shutter 2. Detailed information on each parameter can be found below.

Parameter Description
3: Reports type value should be set to 1 if the module operates in Venetian Blind mode.
10: Roller Shutter operating modes  
12: Turning time/ delay time depending on mode, turning time or delay time
13: Lamellas positioning mode Parameter influences the lamellas positioning in venetian blind mode
14: Switch type either Toggle switches or a single, momentary switch.
17: Delay time after S2 delay till auto turned off or auto gate close
18: Motor operation detection Power threshold to be interpreted as reaching a limit switch.
22: Motor operation time Time period for the motor to continue operation.
29: Forced Roller Shutter calibration set to 1 will enter calibration mode
30: Response to General Alarm  
31: Response to Water Flood Alarm  
32: Response to Smoke, CO, CO2 Alarm  
33: Response to Temperature Alarm  
35: Managing lamellas in response to alarm 0 no change, 1 extreme position
40: Power reports change that needs to occur to trigger the power report
42: Periodic power or energy reports Time to the next report. Value of 0 means the reports are turned off.
43: Energy reports Energy threshold to trigger report
44: Self-measurement if power and energy reports are to sent to the main controller
50: Scenes/ Associations activation whether scenes or associations are activated by the switch keys
1: Momentary click  
2: Momentary hold  
3: Controller Updates  

3: Reports type

value should be set to 1 if the module operates in Venetian Blind mode.

Property Value      
Configuration ID config_3_1      
Data Type INTEGER   Default Value 0
Options Blind position using Z-Wave Command (0)      
  Blind position via Fibar Command (1)      

10: Roller Shutter operating modes

Property Value      
Configuration ID config_10_1      
Data Type INTEGER   Default Value 1
Options Roller Blind Mode, without positioning (0)      
  Roller Blind Mode, with positioning (1)      
  Venetian Blind Mode, with positioning (2)      
  Gate Mode, without positioning (3)      
  Gate Mode, with positioning (4)      

12: Turning time/ delay time

depending on mode, turning time or delay time

Overview

In Venetian Blind mode (parameter 10 set to 2) the parameter determines time of full turn of the lamellas.

In Gate Mode (parameter 10 set to 3 or 4) the parameter defines the delay time after which an open gate starts closing.Type range

Property Value
Configuration ID config_12_2
Data Type INTEGER
Range 0 to 65535
Default Value 150

13: Lamellas positioning mode

Parameter influences the lamellas positioning in venetian blind mode

Overview

Parameter influences the lamellas positioning in venetian blind mode (parameter 10 set to 2)

Set slats back to previous position. In Venetian Blind Mode (parameter 10 set to 2) the parameter influences slats positioning in various situations. In any other operating mode the parameter value is irrelevant.
0 - Slats return to previously set position only in case of the main controller operation.
1 - Slats return to previously set position in case of the main controller operation, momentary switch operation, or when the limit switch is reached.
2 - Slats return to previously set position in case of the main controller operation, momentary switch operation, when the limit switch is reached or after receiving a “STOP” control frame (Switch Multilevel Stop).

Default setting: 1 Parameter size: 1 [byte]

Property Value      
Configuration ID config_13_1      
Data Type INTEGER   Default Value 2
Options only in case of the main controller operation (0)      
  default - controller+switchlimit (1)      
  like 1 + STOP control frame (2)      

14: Switch type

either Toggle switches or a single, momentary switch.

Overview
  1. Switch type. The parameter settings are relevant for Roller Blind Mode and Venetian Blind Mode (parameter 10 set to 0, 1, 2). 0 - Momentary switches 1 - Toggle switches 2 - Single, momentary switch. (The switch should be connected to S1 terminal) Default setting: 0 Parameter size: 1 [byte]
Property Value      
Configuration ID config_14_1      
Data Type INTEGER   Default Value 0
Options Momentary switches (0)      
  Toggle switches (1)      
  Single, momentary switch. (2)      

17: Delay time after S2

delay till auto turned off or auto gate close

Overview
  1. In Roller Blind Mode or Venetian Blind mode (parameter 10 set to 0, 1, 2) the parameter determines when the Roller Shutter relays are turned off after reaching a limit switch. In Gate Mode (parameter 10 set to 3 or 4) the parameter determines a time period after which a gate will start closing after a S2 contact has been disconnected. In this mode, time to turn off the Roller Shutter relays after reaching a limit switch is set to 3 seconds and cannot be modified.

Value of 0 means the gate will note close automatically.
Available settings: 0 - 255 (0,1-25,5s).
Default setting: 10 (1s).
Parameter size: 1 [byte]

Property Value
Configuration ID config_17_1
Data Type INTEGER
Range 0 to 255
Default Value 10

18: Motor operation detection

Power threshold to be interpreted as reaching a limit switch.

Property Value
Configuration ID config_18_1
Data Type INTEGER
Range 0 to 255
Default Value 10

22: Motor operation time

Time period for the motor to continue operation.

Property Value
Configuration ID config_22_2
Data Type INTEGER
Range 0 to 65535
Default Value 10

29: Forced Roller Shutter calibration

set to 1 will enter calibration mode

Overview
  1. Forced Roller Shutter calibration. By modifying the parameters setting from 0 to 1 a Roller Shutter enters the calibration mode. The parameter relevant only if a Roller Shutter is set to work in positioning mode (parameter 10 set to 1, 2 or 4). 1 - Start calibration process Default setting: 0 Parameter size: 1 [byte]
Property Value      
Configuration ID config_29_1      
Data Type INTEGER   Default Value 0
Options Deactivated (0)      
  Start calibration process (1)      

30: Response to General Alarm

Property Value      
Configuration ID config_30_1      
Data Type INTEGER   Default Value 2
Options No response to alarm frames (0)      
  Open Blind (1)      
  Close Blind (2)      

31: Response to Water Flood Alarm

Property Value      
Configuration ID config_31_1      
Data Type INTEGER   Default Value 0
Options No response to alarm frames (0)      
  Open Blind (1)      
  Close Blind (2)      

32: Response to Smoke, CO, CO2 Alarm

Property Value      
Configuration ID config_32_1      
Data Type INTEGER   Default Value 1
Options No response to alarm frames (0)      
  Open Blind (1)      
  Close Blind (2)      

33: Response to Temperature Alarm

Property Value      
Configuration ID config_33_1      
Data Type INTEGER   Default Value 1
Options No response to alarm frames (0)      
  Open Blind (1)      
  Close Blind (2)      

35: Managing lamellas in response to alarm

0 no change, 1 extreme position

Overview
  1. Managing slats in response to alarm. In Venetian Blind Mode (parameter 10 set to 2), the parameter determines how the slats will react upon alarm detection. In any other modes, the parameter value is not relevant. 0 - Do not change slats position - slats return to the last set position. 1 - Set slats to their extreme position. Default setting: 1 Parameter size: 1 [byte]
Property Value      
Configuration ID config_35_1      
Data Type INTEGER   Default Value 1
Options Do not change lamellas position (0)      
  Set lamellas to their extreme position (1)      

40: Power reports

change that needs to occur to trigger the power report

Overview
  1. Power reports. Power level change that will result in new power value report being sent. The parameter defines a change that needs to occur in order to trigger the report. The value is a percentage of the previous report. Power report threshold available settings: 1-100 (1-100%). Value of 0 means the reports are turned off. Default setting: 10 (10%). Parameter size: 1 [byte]
Property Value
Configuration ID config_40_1
Data Type INTEGER
Range 0 to 100
Default Value 10

42: Periodic power or energy reports

Time to the next report. Value of 0 means the reports are turned off.

Property Value
Configuration ID config_42_2
Data Type INTEGER
Range 0 to 65534
Default Value 3600

43: Energy reports

Energy threshold to trigger report

Overview
  1. Energy reports. Energy level change which will result in new energy value report being sent. The parameter defines a change that needs to occur in order to trigger the report. Energy threshold available settings: 1-254 (0,01 - 2,54kWh). Value of 0 means the reports are turned off. Default setting 10 (0,1kWh). Parameter size: 1 [byte]
Property Value
Configuration ID config_43_1
Data Type INTEGER
Range 0 to 254
Default Value 10

44: Self-measurement

if power and energy reports are to sent to the main controller

Overview
  1. Self-measurement. A Roller Shutter may include power and energy used by itself in reports sent to the main controller.
    0 - Self-measurement inactive.
    1 - Self-measurement active.
    Default setting: 0
    Parameter size: 1 [byte] 
Property Value      
Configuration ID config_44_1      
Data Type INTEGER   Default Value 0
Options Disabled (0)      
  Activated (1)      

50: Scenes/ Associations activation

whether scenes or associations are activated by the switch keys

Overview

SCENES AND ASSOCIATIONS SETTINGS:

  1. Scenes / Associations activation. Parameter determines whether scenes or associations are activated by the switch keys.
    0 - Associations activation
    1 - Scenes activation
    Default setting: 0
    Parameter size: 1 [byte]
Property Value      
Configuration ID config_50_1      
Data Type INTEGER   Default Value 0
Options Associations Active (0)      
  Scenes Active (1)      

1: Momentary click

Property Value
Configuration ID group_1
Data Type TEXT
Range to

2: Momentary hold

Property Value
Configuration ID group_2
Data Type TEXT
Range to

3: Controller Updates

Property Value
Configuration ID group_3
Data Type TEXT
Range to

Did you spot an error in the above definition or want to improve the content? You can edit the database here.