SES 303 Temperature and humidity sensor

This describes the Z-Wave device SES 303, manufactured by Horstmann Controls Limited with the thing type UID of horstmann_ses303_00_000.

Temperature and humidity sensor

Channels

The following table summarises the channels available for the SES 303 Temperature and humidity sensor.

Channel Channel Id Channel Type UID Category Item Type
Sensor (temperature) sensor_temperature sensor_temperature Temperature Number
Sensor (relative humidity) sensor_relhumidity sensor_relhumidity Humidity Number
  battery-level system.battery-level    

Sensor (temperature)

Scale

Select the scale for temperature readings

Property Value      
Configuration ID config_scale      
Data Type TEXT   Default Value 0
Options Celsius (0)      
  Fahrenheit (1)      

Device Configuration

The following table provides a summary of the configuration parameters available in the SES 303 Temperature and humidity sensor. Detailed information on each parameter can be found below.

Parameter Description
1: Delta Temp Precision of measured temperature (delta)
2: Temp Reporting Interval Reporting interval in minutes
3: Delta Humidity Precision of measured humidity (delta)
4: Humidity Reporting Interval Reporting interval in minutes

1: Delta Temp

Precision of measured temperature (delta)

Overview

Configuration value : Desired value / Resolution. (Resolution = 0.1)

Example: To configure Delta temperature to 2 °C,  the value needed to be configured in device is 2/0.1 = 20.

IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128…255, the value sent in the application shall be equal to desired value minus 256. For example, to set Delta Temperature to 130, it may be needed to set a value 130−256=−126.

Zero configuration means that the corresponding functionality is disabled.

Property Value
Configuration ID config_1_1
Data Type INTEGER
Range 0 to 255
Default Value 0

2: Temp Reporting Interval

Reporting interval in minutes

Overview

IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128…255, the value sent in the application shall be equal to desired value minus 256. For example, to set Delta Temperature to 130, it may be needed to set a value 130−256=−126.

Zero configuration means that the corresponding functionality is disabled.

Property Value
Configuration ID config_2_1
Data Type INTEGER
Range 0 to 255
Default Value 5

3: Delta Humidity

Precision of measured humidity (delta)

Overview

Configuration value : Desired value / Resolution. (Resolution = 0.1)

Example: To configure Delta temperature to 2 °C,  the value needed to be configured in device is 2/0.1 = 20.

IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128…255, the value sent in the application shall be equal to desired value minus 256. For example, to set Delta Temperature to 130, it may be needed to set a value 130−256=−126.

Zero configuration means that the corresponding functionality is disabled.

Property Value
Configuration ID config_3_1
Data Type INTEGER
Range 0 to 255
Default Value 5

4: Humidity Reporting Interval

Reporting interval in minutes

Overview

IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128…255, the value sent in the application shall be equal to desired value minus 256. For example, to set Delta Temperature to 130, it may be needed to set a value 130−256=−126.

Zero configuration means that the corresponding functionality is disabled.

Property Value
Configuration ID config_4_1
Data Type INTEGER
Range 0 to 255
Default Value 5

Did you spot an error in the above definition or want to improve the content? You can edit the database here.