ZTS-110 ZTS-110 Z Wave Thermostat

This describes the Z-Wave device ZTS-110, manufactured by Remotec with the thing type UID of remotec_zts110_00_000.

ZTS-110 Z Wave Thermostat

Channels

The following table summarises the channels available for the ZTS-110 ZTS-110 Z Wave Thermostat.

Channel Channel Id Channel Type UID Category Item Type
Sensor (temperature) sensor_temperature sensor_temperature Temperature Number
Thermostat mode thermostat_mode remotec_zts110_00_000_thermostat_mode Temperature Number
Thermostat Operating State thermostat_state thermostat_state Temperature Number
Setpoint (cooling) thermostat_setpoint_cooling thermostat_setpoint Temperature Number
Setpoint (heating) thermostat_setpoint_heating thermostat_setpoint Temperature Number
Thermostat fan mode thermostat_fanmode remotec_zts110_00_000_thermostat_fanmode Temperature Number
Thermostat fan state thermostat_fanstate remotec_zts110_00_000_thermostat_fanstate Temperature Number
  battery-level system.battery-level    

Sensor (temperature)

Scale

Select the scale for temperature readings

Property Value      
Configuration ID config_scale      
Data Type TEXT   Default Value 0
Options Celsius (0)      
  Fahrenheit (1)      

Setpoint (cooling)

Scale

Select the scale to use for setpoints.

Property Value      
Configuration ID config_scale      
Data Type TEXT   Default Value 0
Options Celsius (0)      
  Fahrenheit (1)      

Setpoint (heating)

Scale

Select the scale to use for setpoints.

Property Value      
Configuration ID config_scale      
Data Type TEXT   Default Value 0
Options Celsius (0)      
  Fahrenheit (1)      

Device Configuration

The following table provides a summary of the configuration parameters available in the ZTS-110 ZTS-110 Z Wave Thermostat. Detailed information on each parameter can be found below.

Parameter Description
1: Swing Set Swing value from 1F/.5C to 4F/2.0C Available settings: 1 - 4
2: Differntial Set Differential value from 1F/.5C to 4F/2.0C Available settings: 1 - 4
3: Set Filter Counter Set filter replacement timer from 500 to 4000 hours.
4: Report Filter Counter READ ONLY: Data in hours
5: Scale of Temperature Set Temperature Scale to Farhenheit or Centigrade. DEFAULT =1 Farhenheit
6: Upper Limit of Setpoint A Determines Upper Limit of set point A. Unit in celsius A=(B+2)min (37.0 C)max, Unit in Fah…
7: Lower Limit of Setpoint B Determines Lower Limit of set point B. Unit in celsius (5.0 C to 35.0 C) Unit in Fahrenhei…
8: Easy Mode Set Easy Mode 0:DISABLE 1:ENABLED DEFAULT:ENABLED
9: Time Format Configures for 12 or 24 Hour format. Default is 12 Hours.
10: Repeat Basic Set Counter Thermostat sends ‘Basic Set’ command to its association node repeatedly ever X minutes. 0 …
11: Trigger AUTO report if room temperature is different from last report. 0 = Disabled or set value from 1 to 8 where each number corresponds to 1 Degree F or .5 De…
12: Sensor temperature calibration. 0 = Disabled or set value from 1 to 10 in 1 degree F increments or -1 to -10 in 1 degree F…
13: AUTO report by time interval. 0 = Disabled or set value from 1 to 16 where 1 = .5 hours and each consecutive number incr…
1: Heat Pump  
2: Compressor  
3: Controller Update  

1: Swing

Set Swing value from 1F/.5C to 4F/2.0C Available settings: 1 - 4

Property Value
Configuration ID config_1_1
Data Type INTEGER
Range 1 to 4
Default Value 2

2: Differntial

Set Differential value from 1F/.5C to 4F/2.0C Available settings: 1 - 4

Property Value
Configuration ID config_2_1
Data Type INTEGER
Range 1 to 4
Default Value 2

3: Set Filter Counter

Set filter replacement timer from 500 to 4000 hours.

Property Value
Configuration ID config_3_2
Data Type INTEGER
Range 500 to 4000
Default Value 500

4: Report Filter Counter

READ ONLY: Data in hours

Property Value
Configuration ID config_4_2
Data Type INTEGER
Range 0 to 9999
Default Value 0

5: Scale of Temperature

Set Temperature Scale to Farhenheit or Centigrade. DEFAULT =1 Farhenheit

Property Value      
Configuration ID config_5_1      
Data Type INTEGER   Default Value 1
Options Centigrade (0)      
  Farhenheit (1)      

6: Upper Limit of Setpoint A

Determines Upper Limit of set point A. Unit in celsius A=(B+2)min (37.0 C)max, Unit in Fahrenheit A=(B+4)min (99.0 F)max

Property Value
Configuration ID config_6_2
Data Type INTEGER
Range 37 to 99
Default Value 99

7: Lower Limit of Setpoint B

Determines Lower Limit of set point B. Unit in celsius (5.0 C to 35.0 C) Unit in Fahrenheit (41.0 F to 95.0 F)

Property Value
Configuration ID config_7_2
Data Type INTEGER
Range 5 to 95
Default Value 41

8: Easy Mode

Set Easy Mode 0:DISABLE 1:ENABLED DEFAULT:ENABLED

Property Value      
Configuration ID config_8_1      
Data Type INTEGER   Default Value 1
Options Easy Mode Disabled (0)      
  Easy Mode Enabled (1)      

9: Time Format

Configures for 12 or 24 Hour format. Default is 12 Hours.

Property Value      
Configuration ID config_9_1      
Data Type INTEGER   Default Value 1
Options 24 Hour Format (0)      
  12 Hour Format (1)      

10: Repeat Basic Set Counter

Thermostat sends ‘Basic Set’ command to its association node repeatedly ever X minutes. 0 = Disabled or Set to Enabled Values available 3 to 255.

Property Value
Configuration ID config_10_1
Data Type INTEGER
Range 0 to 255
Default Value 0

11: Trigger AUTO report if room temperature is different from last report.

0 = Disabled or set value from 1 to 8 where each number corresponds to 1 Degree F or .5 Degrees Celsius.

Property Value
Configuration ID config_11_1
Data Type INTEGER
Range 0 to 8
Default Value 4

12: Sensor temperature calibration.

0 = Disabled or set value from 1 to 10 in 1 degree F increments or -1 to -10 in 1 degree F increments .

Property Value
Configuration ID config_12_1
Data Type INTEGER
Range -10 to 10
Default Value 0

13: AUTO report by time interval.

0 = Disabled or set value from 1 to 16 where 1 = .5 hours and each consecutive number increases time by .5 hours.

Property Value
Configuration ID config_13_1
Data Type INTEGER
Range 0 to 16
Default Value 0

1: Heat Pump

Property Value
Configuration ID group_1
Data Type TEXT
Range to

2: Compressor

Property Value
Configuration ID group_2
Data Type TEXT
Range to

3: Controller Update

Property Value
Configuration ID group_3
Data Type TEXT
Range to

Did you spot an error in the above definition or want to improve the content? You can edit the database here.