Sensoair Air quality sensor for indoor use

This describes the Z-Wave device Sensoair, manufactured by SIEGENIA-AUBI KG with the thing type UID of siegeniaaubi_sensoair_00_000.

Air quality sensor for indoor use

Channels

The following table summarises the channels available for the Sensoair Air quality sensor for indoor use.

Channel Channel Id Channel Type UID Category Item Type
Sensor (CO2) sensor_co2 sensor_co2   Number

Device Configuration

The following table provides a summary of the configuration parameters available in the Sensoair Air quality sensor for indoor use. Detailed information on each parameter can be found below.

Parameter Description
1: Device Configuration Value 1 Configuration of the device operating mode
2: Interval for unsolicited Sensor Report Mode B defines how often a Sensor report is sent
1: Group 1  

1: Device Configuration Value 1

Configuration of the device operating mode

Overview
  • bit 0    Unsolicited Multilevel Report Mode A    0 = disabled, 1 = enabled
  • bit 1    Unsolicited Multilevel Report Mode B    0 = disabled, 1 = enabled
  • bit 2    Basic Set                                         0 = disabled, 1 = enabled
  • bit 3    Broadcast Multilevel Report                 0 = disabled, 1 = enabled
  • bit 7    SENSOAIR LEDs                               0 = disabled, 1 = enabled

Unsolicited Multilevel Report Mode A

SENSOAIR sends an usolicited multilevel report when the CO2 value
exceeds one of the following threshold values:
600 ppm, 800 ppm, 1000 ppm, 1500 ppm, 2000 ppm, 2500 ppm

Unsolicited Multilevel Report Mode B

SENSOAIR sends the current CO2 value (without being requested) in an interval of
5 - 65000 seconds. The interval can be configured with parameter 2.

Property Value
Configuration ID config_1_1
Data Type INTEGER
Range 0 to 143
Default Value 141

2: Interval for unsolicited Sensor Report Mode B

defines how often a Sensor report is sent

Overview

When enabled by parameter 1, SENSOAIR sends the current CO2 value (without being requested) in an interval of 5 - 65000 seconds. The interval (default setting = 30s) is configured as follows:

Device Configuration Value 1 = MSB (default 0x00)

Device Configuration Value 2 = LSB (default 0x1e)

Property Value
Configuration ID config_2_2
Data Type INTEGER
Range 5 to 65000
Default Value 30

1: Group 1

Property Value
Configuration ID group_1
Data Type TEXT
Range to