TF016 ZWave Thermostat

This describes the Z-Wave device TF016, manufactured by ThermoFloor with the thing type UID of thermofloor_tf016_01_008.

ZWave Thermostat

Channels

The following table summarises the channels available for the TF016 ZWave Thermostat.

Channel Channel Id Channel Type UID Category Item Type
Sensor (temperature) sensor_temperature sensor_temperature Temperature Number
Thermostat mode thermostat_mode thermofloor_tf016_01_008_thermostat_mode Temperature Number
Setpoint (heating) thermostat_setpoint_heating thermostat_setpoint Temperature Number
Setpoint (heating economy) thermostat_setpoint_heating_econ thermostat_setpoint Temperature Number
Setpoint (furnace) thermostat_setpoint_furnace thermostat_setpoint Temperature Number
Sensor mode config_decimal_param2 thermofloor_tf016_01_008_config_decimal_param2   Number

Sensor (temperature)

Scale

Select the scale for temperature readings

Property Value      
Configuration ID config_scale      
Data Type TEXT   Default Value 0
Options Celsius (0)      
  Fahrenheit (1)      

Setpoint (heating)

Scale

Select the scale to use for setpoints.

Property Value      
Configuration ID config_scale      
Data Type TEXT   Default Value 0
Options Celsius (0)      
  Fahrenheit (1)      

Setpoint (heating economy)

Scale

Select the scale to use for setpoints.

Property Value      
Configuration ID config_scale      
Data Type TEXT   Default Value 0
Options Celsius (0)      
  Fahrenheit (1)      

Setpoint (furnace)

Scale

Select the scale to use for setpoints.

Property Value      
Configuration ID config_scale      
Data Type TEXT   Default Value 0
Options Celsius (0)      
  Fahrenheit (1)      

Device Configuration

The following table provides a summary of the configuration parameters available in the TF016 ZWave Thermostat. Detailed information on each parameter can be found below.

Parameter Description
1: Operation mode  
2: Sensor mode  
3: Floor sensor type  
4: DIFF l. Temperature control Hysteresis Range 3-30 (0.3°C 3.0°C)
5: FLo, Floor min limit Range 50-400 (5.0°C 40.0°C)
6: FHi, Floor max limit Range 50-400 (5.0°C 40.0°C)
7: ALo, Air min limit Range 50-400 (5.0°C 40.0°C)
8: AHi, Air max limit Range 50-400 (5.0°C 40.0°C)
9: PLo, FP-mode P setting  
10: CO mode setpoint Range 50-400 (5.0°C 40.0°C)
11: ECO mode setpoint Range 50-400 (5.0°C 40.0°C)
12: P setting  
13: COOL setpoint Only if cooling enabled. Range 50-400 (5.0°C 40.0°C)
1: Lifeline  
2: On/Off control  

1: Operation mode

Property Value      
Configuration ID config_1_2      
Data Type INTEGER   Default Value 1
Options OFF (0)      
  HEAT (1)      
  COOL (2)      
  ENERGY SAVE HEAT (11)      

2: Sensor mode

Property Value      
Configuration ID config_2_2      
Data Type INTEGER   Default Value 1
Options F-mode (0)      
  A-mode (1)      
  AF-mode (2)      
  A2-mode (3)      
  P-mode (4)      
  FP-mode (5)      

3: Floor sensor type

Property Value      
Configuration ID config_3_2      
Data Type INTEGER   Default Value 0
Options 10k NTC (0)      
  12k NTC (1)      
  15k NTC (2)      
  22k NTC (3)      
  33k NTC (4)      
  47k NTC (5)      

4: DIFF l. Temperature control Hysteresis

Range 3-30 (0.3°C 3.0°C)

Property Value
Configuration ID config_4_2
Data Type INTEGER
Range 3 to 30
Default Value 5

5: FLo, Floor min limit

Range 50-400 (5.0°C 40.0°C)

Property Value
Configuration ID config_5_2
Data Type INTEGER
Range 50 to 400
Default Value 50

6: FHi, Floor max limit

Range 50-400 (5.0°C 40.0°C)

Property Value
Configuration ID config_6_2
Data Type INTEGER
Range 50 to 400
Default Value 400

7: ALo, Air min limit

Range 50-400 (5.0°C 40.0°C)

Property Value
Configuration ID config_7_2
Data Type INTEGER
Range 50 to 400
Default Value 50

8: AHi, Air max limit

Range 50-400 (5.0°C 40.0°C)

Property Value
Configuration ID config_8_2
Data Type INTEGER
Range 50 to 400
Default Value 400

9: PLo, FP-mode P setting

Property Value
Configuration ID config_9_2
Data Type INTEGER
Range 0 to 9
Default Value 0

10: CO mode setpoint

Range 50-400 (5.0°C 40.0°C)

Property Value
Configuration ID config_10_2
Data Type INTEGER
Range 50 to 400
Default Value 210

11: ECO mode setpoint

Range 50-400 (5.0°C 40.0°C)

Property Value
Configuration ID config_11_2
Data Type INTEGER
Range 50 to 400
Default Value 180

12: P setting

Property Value
Configuration ID config_12_2
Data Type INTEGER
Range 0 to 10
Default Value 2

13: COOL setpoint

Only if cooling enabled. Range 50-400 (5.0°C 40.0°C)

Property Value
Configuration ID config_13_2
Data Type INTEGER
Range 50 to 400
Default Value 210

1: Lifeline

Property Value
Configuration ID group_1
Data Type TEXT
Range to

2: On/Off control

Property Value
Configuration ID group_2
Data Type TEXT
Range to