ZSE40 4-in-1 Sensor

This describes the Z-Wave device ZSE40, manufactured by Zooz with the thing type UID of zooz_zse40_00_000.

4-in-1 Sensor

Channels

The following table summarises the channels available for the ZSE40 4-in-1 Sensor.

Channel Channel Id Channel Type UID Category Item Type
Motion sensor_binary sensor_binary Door Switch
Binary Sensor sensor_binary sensor_binary Door Switch
Sensor (relative humidity) sensor_relhumidity sensor_relhumidity Humidity Number
Sensor (luminance) sensor_luminance sensor_luminance Temperature Number
Sensor (temperature) sensor_temperature sensor_temperature Temperature Number
Alarm (motion) alarm_motion alarm_motion Door Switch
Alarm (tamper) alarm_tamper alarm_tamper   Switch
  battery-level system.battery-level    

Sensor (temperature)

Scale

Select the scale for temperature readings

Property Value      
Configuration ID config_scale      
Data Type TEXT   Default Value 0
Options Celsius (0)      
  Fahrenheit (1)      

Device Configuration

The following table provides a summary of the configuration parameters available in the ZSE40 4-in-1 Sensor. Detailed information on each parameter can be found below.

Parameter Description
1: Temperature Scale Set the temperature scale
2: Temperature offset temperature change to be reported
3: Humidity Configure Relative Humidity
4: Light Sensor Configure Light Sensor
5: Trigger Interval Set the trigger interval for motion sensor re-activation.
6: Motion Sensor Sensitivity Adjust sensitivity of the motion sensor.
7: LED indicator mode Select the LED indicator mode
1: Receive updates Receive sensor updates

1: Temperature Scale

Set the temperature scale

Property Value      
Configuration ID config_1_1      
Data Type INTEGER   Default Value 0
Options Celsius (0)      
  Fahrenheit (1)      

2: Temperature offset

temperature change to be reported

Overview

Use it to set temperature change to be reported by the sensor. Values: 1 - 50 (where 1 stands for 0.1 degree and 50 stands for 5 degrees). Default set to 1 degree (value 10). The sensor will report new temperature value to the controller whenever temperature goes 1 degree up or down. 

Property Value
Configuration ID config_2_1
Data Type INTEGER
Range 0 to 50
Default Value 1

3: Humidity

Configure Relative Humidity

Overview

Use it to set humidity percentage change to be reported by the sensor. Values: 1 - 50 where 1 stands for 1% and 50 stands for 50%. Default set to 10%.

Property Value
Configuration ID config_3_1
Data Type INTEGER
Range 1 to 50
Default Value 10

4: Light Sensor

Configure Light Sensor

Overview

Reports light level in percentage (1-100). Use it to choose light percentage change to be reported by the sensor. Values: 5 - 50 where 5 stands for 5% and 50 stands for 50%. Default set to 10%. 

Property Value
Configuration ID config_4_1
Data Type INTEGER
Range 1 to 50
Default Value 10

5: Trigger Interval

Set the trigger interval for motion sensor re-activation.

Overview

Use it to set trigger interval - the time when motion is reported again after initial trigger. Values: 1 - 255 where 1 stands for 1 minute and 255 stands for 255 minutes. Default set to 3 minutes. Size: 1 byte dec. NOTE: Small interval will increase activity and decrease battery life. 

Property Value
Configuration ID config_5_1
Data Type INTEGER
Range 1 to 255
Default Value 3

6: Motion Sensor Sensitivity

Adjust sensitivity of the motion sensor.

Property Value      
Configuration ID config_6_1      
Data Type INTEGER   Default Value 4
Options highest (1)      
  higher (2)      
  high (3)      
  normal (4)      
  low (5)      
  lower (6)      
  lowest (7)      

7: LED indicator mode

Select the LED indicator mode

Overview

LED indicator will flash every 3 minutes or whenever you press the Z-Wave button to indicate temperature level.

Green = under 60°F

Blue = 60°-75°F

Yellow = 75°-83°F

Purple = 83°-97°F

Red = over 97°F / motion detected / tamper switch triggered 

Property Value      
Configuration ID config_7_1      
Data Type INTEGER   Default Value 3
Options Off (1)      
  Pulsing Temperature, Flashing Motion (2)      
  Flashing Temperature and Motion (3)      
  No Temperature, Flashing Motion (4)      

1: Receive updates

Receive sensor updates

Property Value
Configuration ID group_1
Data Type TEXT
Range to

Did you spot an error in the above definition or want to improve the content? You can edit the database here.