ZME_05431 Flush mountable switch

This describes the Z-Wave device ZME_05431, manufactured by Z-Wave.Me with the thing type UID of zwaveme_zme05431_00_000.

Flush mountable switch

Channels

The following table summarises the channels available for the ZME_05431 Flush mountable switch.

Channel Channel Id Channel Type UID Category Item Type
Switch switch_binary switch_binary Switch Switch
Scene Number scene_number scene_number   Number

Device Configuration

The following table provides a summary of the configuration parameters available in the ZME_05431 Flush mountable switch. Detailed information on each parameter can be found below.

Parameter Description
1: Set LED indication mode  
2: Automatic switch off If not zero, automatically switch off after a user defined time
3: Function of RF off command Defines how to interpret RF Off command. Can be used in conjunction with Auto Off function…
4: Switch on dimming by buttons Defines if the switch should change it state to on/off if it is dimmed by buttons
5: Switch on dimming by buttons Defines if the switch should restore switch state to the last state prior to device power …
10: Typical click timeout Typical time used to differentiate click, hold, double and triple clicks
11: Invert buttons  
12: Switch by buttons If disabled, the local operations by buttons will not switch the load, but only send comma…
13: Action on button single press or hold Defines which command should be sent on button single press or hold. Basic commands are se…
14: Action on button double press or hold Defines which command should be sent on button double press or press-hold. Basic commands …
15: Send the following switch all commands  
16: What to do on button Down press  
1: Group 1  
2: Group 2  
3: Group 3  

1: Set LED indication mode

Property Value      
Configuration ID config_1_1      
Data Type INTEGER   Default Value 3
Options Disabled (0)      
  Show switch state (1)      
  Night mode (2)      
  Remote by indicator command class (3)      

2: Automatic switch off

If not zero, automatically switch off after a user defined time

Property Value
Configuration ID config_2_2
Data Type INTEGER
Range 0 to 65535
Default Value 0

3: Function of RF off command

Defines how to interpret RF Off command. Can be used in conjunction with Auto Off function: Ignore - to switch on the light by motion detectors and switch it off after some amount of time: in case of multiple motion detectors each would try to switch the

Property Value      
Configuration ID config_3_1      
Data Type INTEGER   Default Value 0
Options Switch OFF (0)      
  Ignore (1)      
  Switch ON (2)      
  Switch on if load is off else switch off (3)      

4: Switch on dimming by buttons

Defines if the switch should change it state to on/off if it is dimmed by buttons

Property Value      
Configuration ID config_4_1      
Data Type INTEGER   Default Value 1
Options No (0)      
  Yes (Default) (1)      

5: Switch on dimming by buttons

Defines if the switch should restore switch state to the last state prior to device power off (power cycle).

Property Value      
Configuration ID config_5_1      
Data Type INTEGER   Default Value 1
Options No, turn off (0)      
  Yes (Default) (1)      

10: Typical click timeout

Typical time used to differentiate click, hold, double and triple clicks
Defined in 10ms ticks.

Property Value
Configuration ID config_10_1
Data Type INTEGER
Range 1 to 100
Default Value 50

11: Invert buttons

Property Value      
Configuration ID config_11_1      
Data Type INTEGER   Default Value 0
Options No (0)      
  Yes (1)      

12: Switch by buttons

If disabled, the local operations by buttons will not switch the load, but only send commands to On/Off association group. In this mode buttons are not linked with the switch anymore. They can be used separately: buttons to control remote device, switch w

Property Value      
Configuration ID config_12_1      
Data Type INTEGER   Default Value 1
Options No (0)      
  By single press and hold (1)      
  By double press and hold (2)      

13: Action on button single press or hold

Defines which command should be sent on button single press or hold. Basic commands are sent to Association group. Switch All commands are sent broadcast.

Property Value      
Configuration ID config_13_1      
Data Type INTEGER   Default Value 4
Options Disabled (0)      
  Switch On, Off and dim using Basic Set (1)      
  Switch All (2)      
  Send Scenes (3)      
  Switch On/Off and Dim (send Basic Set and Switch Multilevel) (Default) (4)      
  Send Preconfigured Scenes (5)      

14: Action on button double press or hold

Defines which command should be sent on button double press or press-hold. Basic commands are sent to Association group. Switch All commands are sent broadcast. If not disabled, the device will wait for a click timeout to see if the second click would be

Property Value      
Configuration ID config_14_1      
Data Type INTEGER   Default Value 0
Options Disabled (Default) (0)      
  Switch On, Off and dim using Basic Set (1)      
  Switch All (2)      
  Send Scenes (3)      
  Switch On/Off and Dim (send Basic Set and Switch Multilevel) (4)      
  Send Preconfigured Scenes (5)      

15: Send the following switch all commands

Property Value      
Configuration ID config_15_1      
Data Type INTEGER   Default Value 1
Options Switch all on and off (-1)      
  Switch off only (0)      
  Switch on only (1)      

16: What to do on button Down press

Property Value      
Configuration ID config_16_1      
Data Type INTEGER   Default Value 1
Options Switch off (Default) (0)      
  Switch On if load is Off, else switch Off (1)      
  Switch on (2)      

1: Group 1

Property Value
Configuration ID group_1
Data Type TEXT
Range to

2: Group 2

Property Value
Configuration ID group_2
Data Type TEXT
Range to

3: Group 3

Property Value
Configuration ID group_3
Data Type TEXT
Range to

Did you spot an error in the above definition or want to improve the content? You can edit the database here.